What is Power Factor
What is power factor - Power factor is defined as the ratio of real
power to apparent power in the circuit. Power in the circuit are Apparent Power
(VA), Real Power (Watt), and Reactive Power (VAR).
In an electric power system, a load
with a low power factor draws more current than a load with a high power factor
for the same amount of useful power transferred. The higher currents increase
the energy lost in the distribution system, and require larger wires and other
equipment. Because of the costs of larger equipment and wasted energy,
electrical utilities will usually charge a higher cost to industrial or
commercial customers where there is a low power factor.
Figure 1 |
Instantaneous and average power
calculated from AC voltage and current with a zero power factor (Φ = 90, Cos Φ = 0). The blue line shows
all the power is stored temporarily in the load during the first quarter cycle
and returned to the grid during the second quarter cycle, so no real power is
consumed.
Figure 2 |
[Figure 2]
Instantaneous and average power calculated from AC voltage
and current with a lagging power factor (Φ = 45, Cos Φ = 0.71). The blue line shows
some of the power is returned to the grid during the part of the cycle labelled
φ
S = Apparent Power ;
P = Real Power ; Q = Reactive Power
Also by the theorem of Pythagoras,
S2 = P2+Q2
Another theorem:
S = P + Q
S = Cos Φ . P
MOTOR POWER FACTOR
The power factor for a three-phase electric motor can be
expressed as:
PF = P / (V I √3), where,
P = power applied /
real power (W, watt)
V = voltage (V, volts)
I = current (A, ampere)
PF = power factor
For instance, an industrial plant draws 300 A at 380 V and the supply
transformer and backup UPS is rated 300 A x 380 V = 114 kVA. If the power factor of the loads is only 0.8. So,
91,2 KW of real power is consumed by system.
LEADING AND LAGGING CURRENT
Leading current is when voltage leads the current in an
inductor. Lagging current is when current leads the voltage in a capacitor. Practical
loads have resistance, inductance, and capacitance.
- Resistance - with a purely resistive load current and voltage changes polarity in step and the power factor will be 1. Electrical energy flows in a single direction across the network in each cycle.
- Inductance loads - transformers, motors and wound coils – consumes reactive power with current waveform lagging the voltage.
- Capacitance loads - capacitor banks or buried cables – generates reactive power with current phase leading the voltage.
Note:
Just remember ELI the ICE man" or "ELI on ICE"
where,
E = voltage
I = current
L = inductor
C = capacitive
ELI = E is the first letter and I is the last. So, E leads I
in the L (inductor).
ICE = I is the first letter and E is the last. So, I leads E
in the C (capacitor).
Power Factor is an real power to apparent power in the circuit.
ReplyDeletehome electrical wiring | home electrical Repair
I seriously loved reading your thoughts, obviously you really know what are you referring to! Your site is so user friendly too, I have bookmark it in my folder
ReplyDeletecommercial electrician
Happy to hear that you’re on this location, all the best
ReplyDeleteelectricians services